Single Channel Interface Module with Quad Output HS-530
Key Features:
- Enveloped ‘g’ Output
- Input – 100mV/g constant current accelerometers (HS-100 Series)
- Output – AC and 0-10 Volts proportional to either RMS Velocity, Envelope ‘g’, AC ‘g’ via BNC (for data collection), or AC Enveloped ‘g’
- ‘Sensor OK’ Function
- DIN Rail Mounted
Typical Applications:
Fans, pumps, motors, gearboxes, compressore, centrifuges, conveyors, Air handlers, rolls, dryers, presses, cooling, VAC, spindles, machine tooling, process equipment.
Technical Performance |
---|
Input: 100 mV/g constant current accelerometer |
(other sensitivities available) |
Frequency Range: 10 Hz to 10 kHz (-3dB) |
Output 1: Input Filters 500 Hz to 10 kHz (-3dB) |
2-pole Butterworth |
Output 2: Post-Envelope Filter 10 Hz to 1 kHz (-3dB) |
2-pole Butterworth |
Velocity Filters: 10 Hz to 1 kHz (-3dB) 2-pole Butterworth |
Mechanical |
---|
Case Material: Plastic |
Mounting: DIN Rail TS35 (Top Hat) |
Dimensions: 134 x 99 x 22.5 mm (H x D x W) including BNC |
Connections: Screw Clamp |
Conductor Size: 0.5 to 4.0 mm |
Weight: 140 gms (nom) |
Electrical |
---|
Power Input: +24 V DC at 50 mA (HS-570 Power Supply Module) |
Output 1: 0-10 VDC = 0-20 mm/s rms Velocity |
(other ranges available) |
Output 2: 0-10 VDC = 0-10 gE (other ranges available) |
Output 3: (BNC): Buffered acceleration output with DC bias voltage |
(nom. 12 VDC) |
AC only about 0 V on request |
Output 4: Buffered gE AC output with 9 VDC Ref. Voltage |
TDX OK (BNC): Transducer OK. Outputs held at 0 V if in fault |
Environmental |
---|
Operating Temperature Range: 0 to 50ºC |
Installation Category (IEC664): II |
Equipment Class (IEC536): III |
EMC: EN61326-1:2013 |
How to order: