CMCP560 RTD Temperature Transmitter/Monitor

Temperature Transmitter/Monitor CMCP560 RTD

 

Key features:

  • RTD Input
  • Temperature Output
  • Transmitter or Monitor
  • Voltage Detection
  • 100 Ohm Plat. Standard
  • 4-20 mA Output
  • 2 Buffered Outputs
  • 5 Selectable Ranges
  • Fault (OK) Detection
  • CSA & UL C1,D2
  • DIN Rail Mount.
    CMCP560 RTD Temperature Transmitter is compatible with 100 Ohm Platinum 3 wire RTD’s. Available in English scaling, the CMCP560 checks for faults, processes the temperature signal to determine overall amplitude, and outputs a 4-20 mA dc current that is proportional to a range of 0 to 250° F (-17.7 to 121° C). Combining transmitters with an existing PLC or DCS system results in a high density, low cost temperature monitoring system.
The Optional Alarm Module provides ok, alert and danger relays, selectable time delay, trip multiply, bypass and 0 to 5 VDC outputs for displays. The relay outputs can be used to trigger machine shut-down or other alarms. Combining transmitters with an existing PLC or DCS system results in a high density, low cost vibration monitoring system.

Alarms relays and trip multiply are available with the Monitor version.

CMCP500 Monitor Approval LabelAlarms – The CMCP500A Series Monitors have two independent set points, with LED alarm indicators and output relay contacts (Alert and Danger). Set points are adjustable via potentiometer, from 0 to 110% of full scale. Each has an adjustable delay of 1 to 10 seconds. SPST Relay contacts are rated 5 Amps @ 30 Vdc or 250 Vac for resistive loads. Relay contacts can be independently configured by the user for either Normally Open (NO) (Standard) or Normally Closed (NC) operation. Relays are normally de-energized and can be configured for latching or non-latching (standard) operation. Latched alarms may be reset locally or by remote contact closure.

Trip Multiply:

The monitors have set point multiplication of 3X via contact closure (2X available). To avoid tripping the alarms during machine start-up.
Custom Input and Output Configurations Available On Request

Fault Detection:

On board fault detection circuitry continuously monitors the transducer for normal operation. If a fault occurs, the output current is reduced to <2 mA to indicate the fault to the readout system. A green LED on the front of the unit is turned off to provide a local indication of the fault.
     

Technical Specs:

 
Electrical
Input:  100 Ohm Platinum RTD
Power: +24 Vdc @ 45 mA max. (30 mA typical)
Protection: Reverse polarity and transient protection
Frequency Response (wo/filters): (-3 dB) 2 Hz to 20 kHz
Buffered Output: BNC Connector 0-20 kHz
Accuracy: 0.5 % of Full Scale Range
Output: 4-20 mA proportional to the full scale range
Maximum Load: 600 Ohms Resistive
Case: Isolated
Range:  English, 0 to 250° F, or Metric, -17.7 to 121° C
Fault Indication: Green LED and 4-20 mA < 2mA
 
 
Optional Relay Module
Alarms: OK, Alert and Danger
Alarm Setpoints: Alert and Danger Adjustable 0 to 110% FS
Trip Multiply: 2X or 3X on Contact Closure
Alarm Relays: OK, Alert and Danger
Form C, SPDT, 5A @ 30 VDC or 250 VAC
Latching or Non-latching, Selectable
Time Delay: 0.1, 1, 3, 6 or 10 Seconds, Selectable
Alarm LED’s: Alert = Yellow, Danger = Red
Display Outputs: 0-5 VDC for Current Value, Alert Setpoint and Danger Setpoint
   
Environmental
Operating Temp.: -20°C to +80° C (-4° F to +176° F)
Storage Temp.: -55°C to +125° C (-67° F to +257° F)
Relative Humidity: 0 – 95% Non-Condensing
   
Physical
Mounting: 32 mm (G style) or 35 mm (T style) DIN Rail
Size: Transmitter 1.0″ Wide x 3.11″ High x 3.95″ Deep
w/Relay Module 1.6″ Wide x 3.11″ High x 3.95″ Deep
   